en:clt:hotspot:software:cltdesigner:manual:modul_wall

This translation is older than the original page and might be outdated. See what has changed.

This is an old revision of the document!


Module "Wall"

Module "Wall"

The input is divided into:

  • wall dimensions and boundary conditions
  • cross section
  • design loads and design factors (cold and in case of fire)
  • stability
  • connection wall floor
  • fire

In the current version, only rectangular wall elements without openings can be calculated. The wall is defined via a wall height and wall length.

wall dimensions and boundary conditions

The bearing of the wall at the top and bottom edges is hinged and the lateral edges are free. These boundary conditions cannot be changed at present.

In this module, the cross section is defined in the direction of the wall length (vertical cross section) and the width of the cross section cannot be changed.

See Module "CLT-Plate 1D - Continuous beam"

The loads entered, are at design level.

The following loads can be applied:

  • vertical load qd
  • horizontal load Hd
  • load q⊥,d perpendicular to the wall

design loads and design factors

Should it be necessary to define an eccentric load application of qd, the input of eqd can be displayed by pressing the button Settings for eccentric load application.

Eccentricity of the vertical load

For the calculation of the tensile force in the anchor it is necessary to know the proportion of the permanent vertical loads (percentage of gd). Since the permanent vertical load has a relieving effect on the anchor force, this is reduced by multiplication with ξ.

By default, the horizontal load is applied at top of the wall, but can be shifted by entering ΔyHd.

Furthermore, the design factors are specified here.

Design loads and design factors must also be specified for the case of fire.

design loads and design factors in case of fire

For the verification of stability, the buckling length coefficients βℓk and in case of fire βℓk,fi have to be defined. The buckling length is then calculated from the buckling length coefficient and the wall height. The buckling coefficient kc, which is required for the verification, is then automatically determined from the buckling length and the specific cross-section.

stability parameters

The straightness factor βc and the conversion factor to the 5% quantile k05 can be changed in the settings.

For the connection in the floor joint, 4 calculation models are currently available:

  • Tension, compression discrete & shear continuously
  • Compression diskret & tension, shear continuously
  • Tension, compression linear & shear continuously
  • Tension, compression, shear continuously

The chosen model should take into account the existing fasteners in the floor joint.

Depending on the selected calculation model, different inputs are required.

Tension, compression discrete & shear continuously

This model should be selected if tie rods and shear angles are used. Here the load widths for compression and tension are to be entered and an edge distance of the tie rod. The distance of the resulting tensile and compressive force is calculated automatically from this.

Tension, compression discrete & shear continuously

Compression diskret & tension, shear continuously

This model assumes continuous tensile force transmission, as for example in the case of the connection with the SHERPA CLT connector. Here, only the load application width of the compression zone has to be defined.

Compression diskret & tension, shear continuously

Tension, compression linear & shear continuously

This model corresponds to the beam theory and should only be used for very narrow wall strips.

Tension, compression linear & shear continuously

Tension, compression, shear continuously

This model corresponds to an approximate solution of a plate loaded in plane.

Tension, compression, shear continuously

See Module "CLT-Plate 1D - Continuous beam"

Fire left / right instead of fire above and below.

The effective stiffnesses of the wall are given in the tab "cross section values" for the full cross section and in case of structural fire design for the charred cross section.

Cross section values

In the "Verification" tab, the calculated utilisation rates for the respective design situation are displayed.

Summary of the results

The normal and shear stresses are given in the tab "Stresses"

Stresses

The distribution of the internal forces ny and nxy over the wall length and my and vy over the wall height are given in the tab "Distribution of internal forces".

Distribuation of internal forces

Analogously, the internal forces in case of fire.

Distribuation of internal forces in case of fire

  • en/clt/hotspot/software/cltdesigner/manual/modul_wall.1621259081.txt.gz
  • Last modified: 2021/05/17 15:44
  • by Alexandra Thiel